Oppermann KRM-X-2-BAC 0.6
24 V AC/DC BACnet, for controlling fans and monitoring ventilation
incl. sampling tube LKR-X 0.6 m
- VdS approval (G219046/G219053)
- Patented single-tube air measurement system
- Pollution indicator in % and alarm at 70%
- Electronic airflow control
- Reset button operable from outside the housing
- Remote reset option via terminals
- Long service life, alarm threshold tracking
- Bus interface RS485 (only -MOD/ -BAC)
Technical Data
Detector type: Scattered light RM 3.3-X (ALN-E)
Power supply KRM-X-1/KRM-X-1-MOD/KRM-X-1-BAC:
230 V AC ± 10%, 50/60 Hz
Power supply KRM-X-2/KRM-X-2-MOD/KRM-X-2-BAC:
24 V AC (16 - 27.6 V AC) or 24 V DC (21.6 - 27.6 V DC)
Rated current: KRM-X-1 /KRM-X-1-MOD/KRM-X-1-BAC: 30 mA
KRM-X-2/KRM-X-2-MOD/KRM-X-2-BAC: 120 mA
Relay outputs: potential-free
Alarm relay latched: 1 changeover contact, 8 A, 250 V AC or 24 V DC
1 N.C. contact, 8 A, 250 V AC or 24 V DC
Pollution relay: 1 N.C. contact, 6 A, 250 V AC or 24 V DC
Operating temperature: -20 °C - +50 °C
Permissible flow: 1 - 20 m/s
Permissible humidity: 10 - 95% non-condensing
Protection class: IP 65
Approvals/Tests: VdS approval G219046, G219053, DIN EN 54-27
LED Display: Degree of pollution %, flashes > 70%
LED in housing: green operation, blue missing airflow, yellow fault, electronics, smoke detector defective red smoke alarm, including pollution > 99%, flashes when attempting to unlock if the detector chamber is not yet empty
Housing: ABS
Dimensions: approx. 271 x 172 x 85 mm (L x W x H)
Cable gland: 3 x M16
Function
The KRM-X duct smoke detector was developed for smoke detection in ventilation ducts. It is a combination of a smoke detector with an adapter system, whose measuring tube and housing have been specially adapted for optimal airflow through the smoke detector. The multi-chamber measuring tube in the air duct transports the air within the air duct along the entire length of the tube via the detector chamber back into the air duct. If smoke is detected, the detector reacts immediately and triggers an alarm. Over time, the detector becomes contaminated. Due to the alarm threshold tracking, the sensitivity remains the same until total contamination. From 70% contamination, the detector triggers and signals this by flashing. If the detector is not replaced, a smoke alarm will be triggered from 99% contamination. The degree of contamination is signaled on a two-line LED display, which flashes at > 70% and the "Dirt" relay drops out. To verify functionality, the device is equipped with electronic airflow monitoring, which illuminates a blue LED at < 1 m/s. The fault LED illuminates if the smoke detector or electronics are defective, or if the smoke detector is missing. The smoke alarm must be reset using the reset button. The function test is also possible with the same button. Actuation works like a smoke alarm. The same function is also achieved when restarting or when opening the bridge between terminals 9 and 10 (remote unlock).