Oppermann KRM-X-1-BAC-DZ 0.6
230 V AC BAC (BACnet) with DIBt approval, for controlling fire/smoke dampers
incl. sampling tube LKR 0.6 m (also optionally available with sampling tube 1.5 m or 3.0 m)
Technical data
Detector type: Scattered light RM 3.3 (ALK-E)
Power supply: 230 V AC +15% / -10%
Rated current: 140 mA
Relay outputs: potential-free
Alarm relay latched:
1 changeover contact, 8 A, 250 V AC 1 normally closed contact, 8 A, 250 V AC or 24 V DC
Contamination relay: 1 normally closed contact, 6 A, 250 V AC or 24 V DC
System fault relay: 1 normally closed contact, 6 A, 250 V AC or 24 V DC
Air flow relay: 1 normally closed contact, 6 A, 250 V AC or 24 V DC
Operating temperature: -20 °C - +50 °C
Permitted flow: 1 - 20 m/s
Permitted humidity: 10 - 95 % non-condensing
Protection class: IP 54, with WDG IP 65
Approvals/Tests: DIBt approval Z-78.6-200, VdS recognition G210059, FprEN5427
LED Display: Contamination level %, flashes > 70 %
LED in housing:
green = operation
blue = missing airflow
yellow = fault, electronics, smoke detector defective
red = smoke alarm, including contamination > 99 %, flashes when attempting to unlock if detector chamber is not yet empty
Adapter housing: ABS
Air sampling tube:
Aluminum/Plastic
Shortest length 160 mm
Standard length 600 mm
Dimensions: 257 x 166 x 77 mm (L x W x H)
Connection screw fitting: 3 x M16
Function
The KRM-DZ duct smoke detector was developed for smoke detection in ventilation ducts. It combines a smoke detector with an adapter system, whose sampling tube and housing have been specially adapted for optimal airflow through the smoke detector.
The air duct sampling tube transports the air within the air duct over the entire length of the tube through the detector chamber and back into the air duct. If smoke is detected, the detector reacts immediately and triggers an alarm. Over time, the detector becomes contaminated. Due to alarm threshold tracking, the sensitivity remains the same until total contamination. From 70% contamination, the detector signals dirt. If the detector is not replaced, a smoke alarm is triggered from 99% contamination. The contamination level is signaled on a two-line LED display, which flashes at > 70%.
To monitor its functionality, the device is equipped with electronic airflow monitoring, which illuminates a blue LED at < 1 m/s. The fault LED illuminates if the smoke detector or electronics are defective, or if the smoke detector is missing. The smoke alarm or a fault must be reset with the reset button. The same button can also be used for functional testing.
Actuation works like a smoke alarm. Furthermore, the same function is achieved on restart by opening the bridge between terminals 9 and 10 (remote unlock).