IT-AT
Couldn't load pickup availability
Oppermann KRM-X-1 0.16
230 V AC, for controlling fans and for ventilation monitoring
incl. sampling tube LKR-X 0.16 m
VdS approval (G219046/G219053)
Patented single-tube air measurement system
Pollution display in % and message at 70 %
Electronic air flow control
Reset button in housing, operable from outside
Remote reset option via terminals
Long service life, alarm threshold tracking
RS485 bus interface (only -MOD/ -BAC)
Technical data
Detector type: scattered light RM 3.3-X (ALN-E)
Power supply KRM-X-1/KRM-X-1-MOD/KRM-X-1-BAC:
230 V AC ± 10 %, 50/60 Hz
Power supply KRM-X-2/KRM-X-2-MOD/KRM-X-2-BAC:
24 V AC (16 ? 27.6 V AC) or 24 V DC (21.6 ? 27.6 V DC)
Rated current: KRM-X-1 /KRM-X-1-MOD/KRM-X-1-BAC: 30 mA
KRM-X-2/KRM-X-2-MOD/KRM-X-2-BAC: 120 mA
Relay outputs: potential-free
Alarm relay latched: 1 changeover contact, 8 A, 250 V AC or 24 V DC
1 N.C. contact, 8 A, 250 V AC or 24 V DC
Pollution relay: 1 N.C. contact, 6 A, 250 V AC or 24 V DC
Operating temperature: -20 °C - +50 °C
Permissible flow: 1 - 20 m/s
Permissible humidity: 10 - 95 % non-condensing
Protection class: IP 65
Approvals/tests: VdS approval G219046, G219053, DIN EN 54-27
LED Display: Pollution level %, flashes > 70 %
LED in housing: green operation, blue missing air flow, yellow fault, electronics, smoke detector defective red smoke alarm, incl. pollution > 99 %, flashes when attempting to unlock if the detector chamber is not yet empty
Housing: ABS
Air measuring tube: aluminium/plastic
Shortest length 160 mm
Standard length 600 mm
Maximum length 3009 mm
Dimensions: approx. 271 x 172 x 85 mm (L x W x H)
Cable gland: 3 x M16
Function
The KRM-X duct smoke detector was developed for smoke detection in ventilation ducts. It is a combination of a smoke detector with an adapter system whose sampling tube and housing have been specially adapted for optimal airflow through the smoke detector. The multi-chamber sampling tube in the air duct transports the air within the air duct along the entire length of the tube via the detector chamber back into the air duct. Upon detecting smoke, the detector reacts immediately and triggers an alarm. Over time, the detector becomes dirty. Due to the alarm threshold tracking, the sensitivity remains the same until total contamination. From 70 % contamination, the detector triggers and signals this by flashing. If the detector is not replaced, a smoke alarm will occur from 99 % contamination. The degree of contamination is signalled on a two-line LED display; at > 70 % this flashes and the "dirt" relay drops out. To demonstrate functionality, the device is equipped with electronic airflow monitoring, which illuminates a blue LED if the flow is < 1 m/s. The fault LED illuminates if the smoke detector or electronics are defective or if the smoke detector is missing. The smoke alarm must be reset using the reset button. The function test can also be carried out with the same button. Activation acts like a smoke alarm. Furthermore, the same function is achieved by restarting or by opening the bridge between terminals 9 and 10 (remote unlocking)