{"product_id":"krm-x-1-dz-0-6","title":"KRM-X-1-DZ 0.6","description":"\u003cp\u003e\u003cstrong\u003eOppermann KRM-1-DZ 0.6\u003cbr\u003e\u003c\/strong\u003e230 V AC with DIBt approval, for controlling fire\/smoke dampers\u003c\/p\u003e\u003cp\u003eincl. sampling tube LKR 0.6 m (also optionally available with sampling tube 1.5 m or 3.0 m)\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eTechnical Data\u003c\/strong\u003e\u003c\/p\u003e\u003cp\u003eDetector type: Scattered light RM 3.3 (ALK-E)\u003cbr\u003ePower supply: 230 V AC ± 10 %, 50\/60 Hz\u003cbr\u003eRated current: 30 mA\u003cbr\u003eRelay outputs: potential-free\u003cbr\u003eAlarm relay latched:\u003cbr\u003e1 changeover contact, 8 A, 250 V AC 1 NC contact, 8 A, 250 V AC or 24 V DC\u003cbr\u003eContamination relay: 1 NC contact, 6 A, 250 V AC or 24 V DC\u003cbr\u003eSystem fault relay: 1 NC contact, 6 A, 250 V AC or 24 V DC\u003cbr\u003eAirflow relay: 1 NC contact, 6 A, 250 V AC or 24 V DC\u003cbr\u003eOperating temperature: -20 °C - +50 °C\u003cbr\u003ePermissible flow: 1 - 20 m\/s\u003cbr\u003ePermissible humidity: 10 - 95 % non-condensing\u003cbr\u003eProtection class: IP 54, with WDG IP 65\u003cbr\u003eApprovals\/tests: DIBt approval Z-78.6-200, VdS recognition G210059, FprEN5427\u003cbr\u003eLED Display: Contamination level %, flashes \u0026gt; 70 %\u003cbr\u003eLED in housing:\u003cbr\u003egreen = operation\u003cbr\u003eblue = missing airflow\u003cbr\u003eyellow = fault, electronics, smoke detector defective\u003cbr\u003ered = smoke alarm, incl. contamination \u0026gt; 99 %, flashes when attempting to unlock if the detector chamber is not yet empty\u003cbr\u003eAdapter housing: ABS\u003cbr\u003eAir measuring tube:\u003cbr\u003eAluminum\/Plastic\u003cbr\u003eShortest length 160 mm\u003cbr\u003eStandard length 600 mm\u003cbr\u003eDimensions: 257 x 166 x 77 mm (L x W x H)\u003cbr\u003eConnection fitting: 3 x M16\u003c\/p\u003e\u003cp\u003e\u003cstrong\u003eFunction\u003c\/strong\u003e\u003c\/p\u003e\u003cp\u003eThe KRM-DZ duct smoke detector was developed for smoke detection in ventilation ducts. It represents a combination of a smoke detector with an adapter system, whose measuring tube and housing have been specially adapted for optimal airflow through the smoke detector.\u003c\/p\u003e\u003cp\u003eThe air duct sampling tube transports the air within the air duct over the entire length of the tube via the detector chamber back into the air duct. Upon detection of smoke, the detector reacts immediately and triggers an alarm. Over time, the detector becomes contaminated. Due to the alarm threshold tracking, the sensitivity remains the same until total contamination. From 70 % contamination, the detector signals contamination. If the detector is not replaced, a smoke alarm occurs from 99 % contamination. The contamination level is signaled on a two-line LED display, which flashes at \u0026gt; 70 %.\u003c\/p\u003e\u003cp\u003eTo monitor functionality, the device is equipped with an electronic airflow monitoring system, which illuminates a blue LED at \u0026lt; 1 m\/s. The fault LED illuminates if the smoke detector or the electronics are defective, as well as if the smoke detector is missing. The reset button must be used to unlock the smoke alarm or a fault. The same button also allows for a functional test.\u003c\/p\u003e\u003cp\u003eActuation has the same effect as a smoke alarm. Furthermore, the same function is achieved upon restart if the bridge between terminals 9 and 10 is opened (remote unlock).\u003c\/p\u003e","brand":"IT-AT","offers":[{"title":"Default Title","offer_id":52584568553819,"sku":"52016","price":931.5,"currency_code":"EUR","in_stock":true}],"thumbnail_url":"\/\/cdn.shopify.com\/s\/files\/1\/1002\/0742\/7931\/files\/52001-24-scaled_23bc8071-e151-4e59-a734-9bd50beb13a7.jpg?v=1773400119","url":"https:\/\/it-at.de\/en\/products\/krm-x-1-dz-0-6","provider":"IT-AT","version":"1.0","type":"link"}